Building Information - Worthington City (45138) - Evening Street Elementary
Program Type
Assessment Only
Setting
Suburban
Assessment Name
Evening Street Elementary
Assessment Date (on-site; non-EEA)
2015-09-23
Kitchen Type
Full Kitchen
Cost Set:
2015
Building Name
Evening Street Elementary
Building IRN
10868
Building Address
885 Evening St
Building City
Worthington
Building Zipcode
43085
Building Phone
(614) 450-4400
Acreage
2.00
Current Grades:
K-6
Teaching Stations
25
Number of Floors
1
Student Capacity
576
Current Enrollment
579
Enrollment Date
2015-09-14
Enrollment Date is the date in which the current enrollment was taken. Number of Classrooms
22
Historical Register
NO
Building’s Principal
Mary Rykowski
Building Type
Elementary Next Page
Building Information - Worthington City (45138) - Evening Street Elementary
Page 1
Report Generated at 23 Dec 2015 10:42
Building Pictures - Worthington City(45138) - Evening Street Elementary(10868)
North elevation photo:
East elevation photo:
South elevation photo:
West elevation photo:
GENERAL DESCRIPTION 49,927 Total Existing Square Footage 1963,1988 Building Dates K-6 Grades 579 Current Enrollment 25 Teaching Stations 2.00 Site Acreage Evening Street Elementary School, which is not on the National Register of Historic Buildings, and originally constructed in 1963, is a 2-story, 49,927 square-foot brick school building located in a suburban residential setting. The existing facility features a conventionally partitioned design. The structure of the Original Building and 1988 Addition contains brick veneer on load bearing masonry wall system type exterior wall construction, with painted CMU type wall construction in the interior. The floor system consists of concrete slab on grade. The roof structure is metal deck on steel joist type construction. The roof over the Original Building is a mechanically attached heat welded membrane roof system that was installed in 2008. The 1988 Addition is a ballasted EPDM roof system that is original to the addition. The ventilation system of the building is inadequate to meet the needs of the users. The Classrooms are undersized in terms of the current standards established by the State of Ohio. Physical Education and Student Dining spaces consist of one Gymnasium and separate Student Dining. The electrical system for the facility is inadequate. The facility is equipped with a non-compliant security system. The building has a non-compliant automatic fire alarm system. The facility is not equipped with an automated fire suppression system. The building is reported to contain asbestos and other hazardous materials. The overall building is not compliant with ADA accessibility requirements. The school is located on two acres of a larger overall shared site adjacent to residential properties. The property and playgrounds are partially fenced for security. Access onto the site is unrestricted. Site circulation is poor. There is no dedicated space for school buses to load and unload on the site separate from other vehicular traffic. Parking for staff, visitors and community events is adequate. No Significant Findings
Previous Page Next Page
Building Pictures - Worthington City(45138) - Evening Street Elementary(10868)
Page 2
Report Generated at 23 Dec 2015 10:42
Building Construction Information - Worthington City (45138) - Evening Street Elementary (10868)
Name
Year Handicapped Access Floors Square Feet Non OSDM Addition
Original Construction 1963 yes
2
42,740 no
Gym Wing
1
7,187 no
1988 yes Previous Page Next Page
Building Construction Information - Worthington City (45138) - Evening Street Elementary (10868)
Page 3
Report Generated at 23 Dec 2015 10:42
Building Component Information - Worthington City (45138) - Evening Street Elementary (10868)
Addition
Auditorium Agricultural Primary Media Vocational Student Indoor Adult Board Outside Auxiliary Fixed Corridors Education Kitchen Natatorium Gymnasium Center Space Dining Tracks Education Offices Agencies Gymnasium Seating Lab
Original Construction (1963)
6211
Gym Wing (1988) Total
1009 0
7,220
1616
2759
1137
1,616 0
2,759
1,137
4310 0
4,310
0
0
0
0
0
0
Master Planning Considerations Previous Page Next Page
Building Component Information - Worthington City (45138) - Evening Street Elementary (10868)
Page 4
Report Generated at 23 Dec 2015 10:42
Existing CT Programs for Assessment Next Page Previous Page Program Type Program Name Related Space Square Feet No Records Found Legend: Not in current design manual In current design manual but missing from assessment
Page 5
Report Generated at 23 Dec 2015 10:42
Main Assessment Menu - Worthington City (45138) - Evening Street Elementary (10868)
Building Summary - Evening Street Elementary (10868) District:
Worthington City
County:
Franklin
Name:
Evening Street Elementary
Contact:
Mary Rykowski
Phone:
(614) 450-4400
Address: 885 Evening St Worthington,OH 43085 Bldg. IRN: 10868 Current Grades
K-6
Acreage:
2.00
Proposed Grades
N/A
Teaching Stations:
25
Current Enrollment
579
Classrooms:
22
Projected Enrollment
N/A
Area: Central Ohio (0)
Date Prepared: 2015-09-23
By:
Brian Rubenstein
Date Revised: 2015-12-22
By:
Holly Grambort
CEFPI Appraisal Summary Section Cover Sheet
Date HA Number of Floors Current Square Feet 1.0 The School Site Original Construction 1963 yes 2 42,740 2.0 Structural and Mechanical Features Gym Wing 1988 yes 1 7,187 3.0 Plant Maintainability Addition
49,927 4.0 Building Safety and Security 5.0 Educational Adequacy
Total
—
—
60
60%
Borderline
200
113
57%
Borderline
100
51
51%
Borderline
200
132
66%
Borderline
200
74
37%
Poor
200
126
63%
Borderline
= Handicapped Access
*Rating
=1 Satisfactory
6.0 Environment for Education
=2 Needs Repair
LEED Observations
—
—
—
=3 Needs Replacement
Commentary
—
—
—
1000
556
56%
FACILITY ASSESSMENT Cost Set: 2015
Total
Rating
—
— — Borderline
Dollar Enhanced Environmental Hazards Assessment Cost Estimates Assessment C $1,646,013.24 - C=Under Contract
A. Heating System
3
B. Roofing
3
C. Ventilation / Air Conditioning
2
D. Electrical Systems
3
E. Plumbing and Fixtures
3
F. Windows
3
G. Structure: Foundation
1
$0.00 -
H. Structure: Walls and Chimneys
2
$81,100.00 -
I. Structure: Floors and Roofs
1
$0.00 -
J. General Finishes
3
$1,325,679.30 -
K. Interior Lighting
3
$249,635.00 -
L. Security Systems
3
$92,364.95 -
M. Emergency/Egress Lighting
3
$49,927.00 -
N. Fire Alarm
3
$74,890.50 -
O. Handicapped Access
3
$108,585.40 -
P. Site Condition
3
$292,481.00 -
Q. Sewage System
1
$0.00 -
R. Water Supply
1
$0.00 -
S. Exterior Doors
3
$34,000.00 -
T. Hazardous Material
3
$69,352.70 -
U. Life Safety
3
$206,260.00 -
V. Loose Furnishings
3
$199,708.00 -
W. Technology
3
$658,037.86 -
X. Construction Contingency / Non-Construction Cost
-
$1,594,630.92 -
Total
— 100
*HA
*Const P/S = Present/Scheduled Construction
-
Points Possible Points Earned Percentage Rating Category
$82,526.90 100.00% $5,000.00 - Renovation Cost Factor $8,121,897.98 $810,315.21 - Cost to Renovate (Cost Factor applied) $301,390.00 - The Replacement Cost Per SF and the Renovate/Replace ratio are only provided when this summary is $240,000.00 - requested from a Master Plan.
$8,121,897.98 Previous Page
Main Assessment Menu - Worthington City (45138) - Evening Street Elementary (10868)
Page 6
Report Generated at 23 Dec 2015 10:42
Main Assessment Menu - Worthington City (45138) - Evening Street Elementary (10868)
Original Construction (1963) Summary District:
Worthington City
County:
Franklin
Name:
Evening Street Elementary
Contact:
Mary Rykowski
Phone:
(614) 450-4400
Address: 885 Evening St Worthington,OH 43085 Bldg. IRN: 10868 Current Grades
K-6
Acreage:
2.00
Proposed Grades
N/A
Teaching Stations:
25
Current Enrollment
579
Classrooms:
22
Projected Enrollment
N/A
Area: Central Ohio (0)
Date Prepared: 2015-09-23
By:
Brian Rubenstein
Date Revised: 2015-12-22
By:
Holly Grambort
CEFPI Appraisal Summary Section Cover Sheet
Date HA Number of Floors Current Square Feet 1.0 The School Site Original Construction 1963 yes 2 42,740 2.0 Structural and Mechanical Features Gym Wing 1988 yes 1 7,187 3.0 Plant Maintainability Addition
49,927 4.0 Building Safety and Security 5.0 Educational Adequacy
Total
—
—
60
60%
Borderline
200
113
57%
Borderline
100
51
51%
Borderline
200
132
66%
Borderline
200
74
37%
Poor
200
126
63%
Borderline
= Handicapped Access
*Rating
=1 Satisfactory
6.0 Environment for Education
=2 Needs Repair
LEED Observations
—
—
—
=3 Needs Replacement
Commentary
—
—
—
1000
556
56%
FACILITY ASSESSMENT Cost Set: 2015
Total
Rating
—
— — Borderline
Dollar Enhanced Environmental Hazards Assessment Cost Estimates Assessment C $1,458,288.80 - C=Under Contract
A. Heating System
3
B. Roofing
3
C. Ventilation / Air Conditioning
2
D. Electrical Systems
3
E. Plumbing and Fixtures
3
F. Windows
3
G. Structure: Foundation
1
$0.00 -
H. Structure: Walls and Chimneys
2
$50,350.00 -
I. Structure: Floors and Roofs
1
$0.00 -
J. General Finishes
3
$1,211,406.00 -
K. Interior Lighting
3
$213,700.00 -
L. Security Systems
3
$79,069.00 -
M. Emergency/Egress Lighting
3
$42,740.00 -
N. Fire Alarm
3
$64,110.00 -
O. Handicapped Access
3
$99,648.00 -
P. Site Condition
3
$270,920.00 -
Q. Sewage System
1
$0.00 -
R. Water Supply
1
$0.00 -
S. Exterior Doors
3
$34,000.00 -
T. Hazardous Material
3
$68,634.00 -
U. Life Safety
3
$183,268.00 -
V. Loose Furnishings
3
$170,960.00 -
W. Technology
3
$563,313.20 -
X. Construction Contingency / Non-Construction Cost
-
$1,404,856.39 -
Total
— 100
*HA
*Const P/S = Present/Scheduled Construction
-
Points Possible Points Earned Percentage Rating Category
$0.00 $5,000.00 - Renovation Cost Factor $693,670.20 - Cost to Renovate (Cost Factor applied)
100.00% $7,155,323.59
$301,390.00 - The Replacement Cost Per SF and the Renovate/Replace ratio are only provided when this summary is $240,000.00 - requested from a Master Plan.
$7,155,323.59
Main Assessment Menu - Worthington City (45138) - Evening Street Elementary (10868)
Page 7
Report Generated at 23 Dec 2015 10:42
Main Assessment Menu - Worthington City (45138) - Evening Street Elementary (10868)
Gym Wing (1988) Summary District:
Worthington City
County:
Franklin
Name:
Evening Street Elementary
Contact:
Mary Rykowski
Phone:
(614) 450-4400
Address: 885 Evening St Worthington,OH 43085 Bldg. IRN: 10868 Current Grades
K-6
Acreage:
2.00
Proposed Grades
N/A
Teaching Stations:
25
Current Enrollment
579
Classrooms:
22
Projected Enrollment
N/A
Area: Central Ohio (0)
Date Prepared: 2015-09-23
By:
Brian Rubenstein
Date Revised: 2015-12-22
By:
Holly Grambort
CEFPI Appraisal Summary Section Cover Sheet
Date HA Number of Floors Current Square Feet 1.0 The School Site Original Construction 1963 yes 2 42,740 2.0 Structural and Mechanical Features Gym Wing 1988 yes 1 7,187 3.0 Plant Maintainability Addition
49,927 4.0 Building Safety and Security 5.0 Educational Adequacy
Total
—
—
60
60%
Borderline
200
113
57%
Borderline
100
51
51%
Borderline
200
132
66%
Borderline
200
74
37%
Poor
200
126
63%
Borderline
= Handicapped Access
*Rating
=1 Satisfactory
6.0 Environment for Education
=2 Needs Repair
LEED Observations
—
—
—
=3 Needs Replacement
Commentary
—
—
—
1000
556
56%
FACILITY ASSESSMENT Cost Set: 2015
Total
Rating
—
— — Borderline
Dollar Enhanced Environmental Hazards Assessment Cost Estimates Assessment C $187,724.44 - C=Under Contract
A. Heating System
3
B. Roofing
3
C. Ventilation / Air Conditioning
2
D. Electrical Systems
3
E. Plumbing and Fixtures
3
F. Windows
3
G. Structure: Foundation
1
$0.00 -
H. Structure: Walls and Chimneys
2
$30,750.00 -
I. Structure: Floors and Roofs
1
$0.00 -
J. General Finishes
3
$114,273.30 -
K. Interior Lighting
3
$35,935.00 -
L. Security Systems
3
$13,295.95 -
M. Emergency/Egress Lighting
3
$7,187.00 -
N. Fire Alarm
3
$10,780.50 -
O. Handicapped Access
3
$8,937.40 -
P. Site Condition
3
$21,561.00 -
Q. Sewage System
1
$0.00 -
R. Water Supply
1
$0.00 -
S. Exterior Doors
3
$0.00 -
T. Hazardous Material
3
$718.70 -
U. Life Safety
3
$22,992.00 -
V. Loose Furnishings
3
$28,748.00 -
W. Technology
3
$94,724.66 -
X. Construction Contingency / Non-Construction Cost
-
$189,774.54 -
Total
— 100
*HA
*Const P/S = Present/Scheduled Construction
-
Points Possible Points Earned Percentage Rating Category
$82,526.90 100.00% $0.00 - Renovation Cost Factor $966,574.40 $116,645.01 - Cost to Renovate (Cost Factor applied) $0.00 - The Replacement Cost Per SF and the Renovate/Replace ratio are only provided when this summary is $0.00 - requested from a Master Plan.
$966,574.40
Main Assessment Menu - Worthington City (45138) - Evening Street Elementary (10868)
Page 8
Report Generated at 23 Dec 2015 10:42
Facility Assessment
A. Heating System Description:
The existing system for the overall facility is a gas fired heating hot water system, installed in 1963, and is in fair condition. The heating and chilled water system in the overall facility is a 2-pipe system, without a capacity for simultaneous heating and cooling operation, which is not compliant with the OSDM requirements for basic system type. The 3 gas fired boilers, manufactured by PK and Thermal Solutions, were installed in 1999 and 2015 and are in good condition. Heating water is distributed to terminal units consisting of unit ventilators, cabinet heaters, unit heaters, fin tubes, and air handlers. The terminal equipment was installed in 1963 and 1999 and is in fair condition. The system does not comply with the 15 CFM per person fresh air requirements of the Ohio Building Code mechanical code and Ohio School Design Manual. The DDC type system temperature controls were installed in 1999 and are in fair condition. The system does feature individual temperature controls in all spaces required by the OSDM. The overall system does not feature any central energy recovery systems. The facility is not equipped with louvered interior doors to facilitate Corridor utilization as return air plenums. The existing system is ducted in the Gymnasium and Cafeteria, but the ductwork cannot be integrated into a possible future system due to arrangement, air volume, and routing of existing ductwork. The existing system is not ducted, and floor to structural deck heights will not accommodate the installation of properly sized ductwork for a future Ohio School Design Manual approved system. The overall heating system is evaluated as being in safe but inefficient working order, and long term life expectancy of the existing system is not anticipated. The structure is equipped with central air conditioning. The site does not contain underground fuel tanks.
Rating:
3 Needs Replacement
Recommendations:
Provide new overall heating, ventilating, and air conditioning system to achieve compliance with Ohio Building Code and Ohio School Design Manual standards. Convert to ducted system to facilitate efficient exchange of conditioned air. Provide architectural soffits to accommodate the installation of ductwork in the Classrooms.
Item
Cost
Unit
Whole Building
HVAC System $26.12sq.ft. (of entire Replacement: building addition) Convert To Ducted $8.00sq.ft. (of entire System building addition) Sum:
Original Construction (1963) 42,740 ft² Required
Gym Wing (1988) 7,187 ft²
Sum
Required
$1,304,093.24(includes demo of existing system and reconfiguration of piping layout and new controls, air conditioning) $341,920.00(includes costs for vert. & horz. chases, cut openings, soffits, etc. Must be used in addition to HVAC System Replacement if the existing HVAC system is non-ducted)
Required
$1,646,013.24 $1,458,288.80
Comments
$187,724.44
Gas Fired Boilers
Air Handler Back to Assessment Summary
Facility Assessment
Page 9
Report Generated at 23 Dec 2015 10:42
Facility Assessment
B. Roofing Description:
The roof over the Original Building is a mechanically attached heat welded membrane roof system that was installed in 2008 and is in fair condition. The 1988 Addition is a ballasted EPDM roof system that is original to the addition and is in poor condition. There are no District reports of current leaking. No signs of past leaking were observed during the physical assessment. Access to the main roof was gained by an access hatch and an access door that are in fair condition. Access to the gymnasium roof was gained by an access hatch in fair condition. Fall safety protection cages are not required, are not provided. There were observations of standing water on the roof. Metal cap flashings and stone copings are in good condition. Roof storm drainage is addressed through a system of gutters and downspouts and roof drains, which are properly located, and in fair condition. The roof is not equipped with overflow roof drains. No problems requiring attention were observed with any roof penetrations. There are not any covered walkways attached to this structure. A 2011 summary of a report provided by the school district states: ’’The roof on Evening Street Elementary consists of two different roof systems. A ballasted EPDM roof system, and a mechanically attached heat welded roof system are installed on this facility. The roof was recently renovated and is in good serviceable condition. The roof area is typical of a school facility and rooftop equipment and projections are moderate. The roof area drains to internal roof drains. The mechanically attached heat welded roof system is in good condition and should afford another 8 to 12 years of satisfactory service life. The ballasted EPDM roofing system is at the end of its useful service life and should be budgeted for replacement in the year 2011. Field seams where observed to be failing at the time of inspection, in addition to failed field seams failed flashings were observed throughout the roofing system. Recently a photovoltaic electrical generating station was installed on the ballasted EPDM roof area. This photovoltaic system will have to be removed prior to roof renovation and then reinstalled after roof renovation in a separate contract. Roof Management’s budget does not include removal and reinstallation of the photovoltaic system.’’
Rating:
3 Needs Replacement
Recommendations:
The roof over the 1988 Addition requires replacement to meet Ohio School Design Manual guidelines due to condition and age of system and projected lifecycle. The photovoltaic system on this roof will need to be removed and reinstalled in conjunction with the roof replacement.
Item
Cost
Unit
$8.70sq.ft. (Qty) Other: Photovoltaic System Removal & $20,000.00per Reinstallaion system Sum:
Whole Building
Original Construction (1963) 42,740 ft²
Membrane (all types):
Gym Wing Sum Comments (1988) 7,187 ft² 7,187 Required $62,526.90(unless under 10,000 sq.ft.) 1 Required
$82,526.90
$0.00
$20,000.00Remove and reinstall photovoltaic system during roof replacement.
$82,526.90
Typical EPDM Roof
Typical Ballasted EPDM Back to Assessment Summary
Facility Assessment
Page 10
Report Generated at 23 Dec 2015 10:42
Facility Assessment
C. Ventilation / Air Conditioning Description:
The overall facility is equipped with a chilled water type central air conditioning system, which is in fair condition. A chiller provides chilled water and pumps are utilized to distribute chilled water to the terminal units. The ventilation system in the overall facility consists of unit ventilators, installed in 1999 and in fair condition, providing fresh air to Classrooms, and air handlers, installed in 1963 and in poor condition, providing fresh air to other miscellaneous spaces such as Gymnasiums and Student Dining. Relief air venting is provided by transfer grilles to corridors. The ventilation system does not meet the Ohio Building Code 15 CFM per occupant fresh air requirement. The overall system is not compliant with Ohio Building Code and Ohio School Design Manual requirements. Dust collection systems are not required in this facility. The Art program is equipped with a kiln, and existing kiln ventilation is inadequate. General building exhaust systems for Restrooms and Storage Rooms are adequately placed, and in fair condition.
Rating:
2 Needs Repair
Recommendations:
Provide an air conditioning system to meet with Ohio Building Code and Ohio School Design Manual requirements. Replace general building exhaust systems located in Restrooms, Storage Rooms, and Custodial Closets. Pricing included in Item A. Provide a kiln exhaust system.
Item
Cost
Unit Whole BuildingOriginal Construction (1963)Gym Wing (1988)Sum Comments 42,740 ft² 7,187 ft² Kiln Exhaust System:$5,000.00each 1 Required $5,000.00 Sum: $5,000.00 $5,000.00 $0.00
Chiller
Cooling Tower Back to Assessment Summary
Facility Assessment
Page 11
Report Generated at 23 Dec 2015 10:42
Facility Assessment
D. Electrical Systems Description:
The electrical system provided to the overall facility is a 120/208-volt, 3-phase, 4-wire, 1,200-amp system installed in 1963, and is in poor condition. Main switch is missing. Shunt trip button system is also tied into solar panel equipment. Power is provided to the school by a multiple utility owned, pole-mounted transformer located in exterior parking garage, and in good condition. The panel system, installed in 1963, is in poor condition, and cannot be expanded to add additional capacity. The Classrooms are not equipped with adequate electrical outlets. The typical Classroom contains 26 general purpose outlets, 2 dedicated outlets for each Classroom computer, and 2 dedicated outlets for each Classroom television. Some Classrooms are equipped with as many as 28 general purpose outlets, while others are equipped with as few as 24 general purpose outlets. There are not any spaces that have no electrical outlets. The Corridors are not equipped with adequate electrical outlets for servicing. Adequate GFI protected exterior outlets are not provided around the perimeter of the building. The facility is not equipped with an emergency generator. Inadequate lightning protection safeguards are provided. The existing facility is not equipped with a Stage. The overall electrical system does not meet Ohio School Design Manual requirements in supporting the current needs of the school, and will be inadequate to meet the facility’s future needs.
Rating:
3 Needs Replacement
Recommendations:
The entire electrical system requires replacement to meet Ohio School Design Manual guidelines for overall capacity, Classroom capacity, due to condition and age, lack of OSDM-required features, and to facilitate the scope of work outlined in Item U.
Item
Cost
System Replacement:
$16.23sq.ft. (of entire building addition)
Sum:
Unit
Whole Building
Original Construction (1963) 42,740 ft² Required
$810,315.21 $693,670.20
Gym Wing (1988) 7,187 ft²
Sum
Comments
Required
$810,315.21(Includes demo of existing system. Includes generator for life safety systems. Does not include telephone or data or equipment) (Use items below ONLY when the entire system is NOT being replaced)
$116,645.01
Main Switchgear
Solar Power Inverter/Switchgear Back to Assessment Summary
Facility Assessment
Page 12
Report Generated at 23 Dec 2015 10:42
Facility Assessment
E. Plumbing and Fixtures Description:
The service entrance is not equipped with a reduced pressure backflow preventer. A water treatment system is not provided. The domestic water supply piping in the overall facility is copper, was installed in 1963, is original to each addition, and is in fair condition. The waste piping in the overall facility is PVC and galvanized, was installed in 1963, and is in fair condition. The facility is equipped with a gas water heater in good condition, with a separate 119-gallon storage tank in good condition. The school contains 2 Large Group Restrooms for boys, 2 Large Group Restrooms for girls, 1 Single Restroom for boys, 1 Single Restroom for girls, 3 Restrooms associated with specialty Classrooms, and 4 Restrooms for staff. Boys’ Large Group Restrooms contain 0 ADA and 4 non-ADA wall mounted flush valve toilets, 3 ADA and 5 non-ADA wall mounted flush valve urinals, as well as 0 ADA and 6 non-ADA wall mounted lavatories. Girls’ Large Group Restrooms contain 0 ADA and 7 non-ADA wall mounted flush valve toilets, as well as 0 ADA and 8 non-ADA wall mounted lavatories. Staff Restrooms contain 0 ADA and 8 non-ADA wall mounted flush valve toilets, 0 ADA and 1 non-ADA wall mounted urinals, as well as 0 ADA and 7 non-ADA wall mounted lavatories. Condition of fixtures is fair. The facility is equipped with 0 ADA and 0 non-ADA drinking fountains, as well as 2 ADA and 4 non-ADA electric water coolers, in fair condition. The 20 Elementary Classrooms are equipped with 20 ADA and 0 non-ADA sink mounted type drinking fountains, in poor condition. The Special Education Classroom is not equipped with the required Restroom. The Kitchen is equipped with the required Restroom, and fixtures are in poor condition. The Health Clinic is equipped with the required Restroom, and fixtures are in poor condition. The Kindergarten is equipped with Restroom facilities, and fixtures are in poor condition. Kitchen fixtures consist of 1 hand sink, 1 double-compartment sink, and 1 triple-compartment sink, which are in fair condition. The Kitchen is not equipped with a satisfactory grease interceptor. The Kitchen is provided the required 140 degree hot water supply via a mixing valve, which is in good condition. The school does not meet the OBC requirements for fixtures. Relative to LEED requirements, the school is not equipped with low flow type fixtures. Per OBC and OSDM requirements this facility should be equipped with 23 toilets, 10 urinals, 31 lavatories, 20 Classroom sink mounted drinking fountains, and 15 electric water coolers. Observations revealed that the school is currently equipped with 22 toilets, 10 urinals, 22 lavatories, 20 Classroom sink mounted drinking fountains, and 6 electric water coolers. ADA requirements are not met for fixtures and drinking fountains (see Item O). Custodial Closets are properly located and are adequately provided with required service sinks or floor drain sinks, which are in poor condition. A Science Classroom, Lab utility sinks, gas connections, compressed air connections, and safety shower / eyewash are not provided, but are not required due to existing grade configuration. Due to existing grade configuration, no Biology or Chemistry Classroom acid waste systems are required. Adequate exterior wall hydrants are provided.
Rating:
3 Needs Replacement
Recommendations:
To facilitate the school’s compliance with OBC and OSFC fixture requirements, provide 11 new toilets, 9 new lavatories, 0 new urinals, 9 new electric water coolers / new lavatory mounted type drinking fountains. Due to age, condition, LEED, and OSFC requirements, provide 33 new toilets, 31 new lavatories, 10 new urinals, 15 new electric water coolers / new lavatory mounted type drinking fountains. Replace sanitary waste piping in the original construction. Provide reduced pressure backflow preventer. Provide a grease interceptor.
Item
Cost
Back Flow Preventer: Sanitary Waste Piping:
$5,000.00unit $3.50sq.ft. (of entire building addition) $3,800.00unit $1,500.00unit
Toilet: Toilet: Urinal: Sink: Sink: Electric water cooler: HIGH BAY/INDUSTRIAL SPACE - LAB TYPES 5,6,7 Grease Trap or Oil Interceptor Sum:
Facility Assessment
Unit
Whole Building
Original Construction Gym Wing (1963) (1988) 42,740 ft² 7,187 ft² 1 Required Required 11 Required 8 Required
$1,500.00unit $2,500.00unit $1,500.00unit $3,000.00unit $6,000.00each
Page 13
Comments
$5,000.00 $149,590.00(remove / replace) $41,800.00(new) $12,000.00(remove / replace) See Item O $13,500.00(remove / replace) $22,500.00(new) $24,000.00(remove / replace) $27,000.00(double ADA) $6,000.00
9 Required 9 Required 16 Required 9 Required 1 Required $301,390.00 $301,390.00
Sum
$0.00
Report Generated at 23 Dec 2015 10:42
Domestic Water Heater
Single-Occupant Restroom
Back to Assessment Summary
Facility Assessment
Page 14
Report Generated at 23 Dec 2015 10:42
Facility Assessment
F. Windows Description:
The Original Building is equipped with aluminum frame windows with single glazed type window system, which was installed in 1963 and is in poor condition. The window system features operable windows throughout the building, and operable windows are equipped with opening limiters in poor condition and insect screens in poor condition. Window system seals are in poor condition, with moderate air and water infiltration being experienced. Window system hardware is in fair condition. The window system features surface mounted blinds, which are in fair condition. The 1963 Original Construction is equipped with an aluminum frame curtain wall system, installed in at an unknown date, and is in fair condition. The 1988 Addition is equipped with aluminum frame windows with double glazed, tempered type window system, which was installed in 1988 and is in good condition. The window system features inoperable windows throughout the addition. Window system seals are in fair condition, with minimal air and water infiltration being experienced. The windows in this addition do not include blinds. This overall facility does not feature any glass block windows. The exterior doors in the Original Building are equipped with hollow metal frame sidelights and transoms with single pane glazing, provided with internal wire mesh, in fair condition. Exterior door vision panels are provided single pane glazing, provided with internal wire mesh, in fair condition. The exterior doors in the 1988 Addition are not equipped with sidelights or transoms. The school does not contain skylights. The school does not contain any clerestories. Interior glass is wired glass safety glazing. Window security grilles are not provided for ground floor windows. There is not a Greenhouse associated with this school.
Rating:
3 Needs Replacement
Recommendations:
Provide a new insulated window system with integral blinds to meet with Ohio School Design Manual requirements in the Original Building. Exterior door replacement is addressed in Item S.
Item
Cost
Unit
Whole BuildingOriginal Construction (1963)Gym Wing (1988)Sum Comments 42,740 ft² 7,187 ft² Insulated Glass/Panels:$60.00sq.ft. (Qty) 4,000 Required $240,000.00(includes blinds) Sum: $240,000.00 $240,000.00 $0.00
Typical Fenestration
Typical Window Back to Assessment Summary
Facility Assessment
Page 15
Report Generated at 23 Dec 2015 10:42
Facility Assessment
G. Structure: Foundation Description:
The Original Building and the 1988 Addition are equipped with concrete masonry unit foundation walls on concrete footings, which displayed no locations of significant differential settlement, cracking, or leaking, and are in fair condition. No significant issues related to foundation cracking or spalling were encountered. The District reports that there has been no past leaking. No grading or site drainage deficiencies were noted around the perimeter of the structure that are contributing or could contribute to foundation and wall structural deterioration.
Rating:
1 Satisfactory
Recommendations:
Existing conditions require no renovation or replacement at the present time.
Item CostUnitWhole BuildingOriginal Construction (1963)Gym Wing (1988)SumComments 42,740 ft² 7,187 ft² Sum: $0.00 $0.00 $0.00
Back to Assessment Summary
Facility Assessment
Page 16
Report Generated at 23 Dec 2015 10:42
Facility Assessment
H. Structure: Walls and Chimneys Description:
The Original Building and 1988 Addition have a brick veneer on load bearing masonry wall system, which displayed minor locations of deterioration, and is in fair condition. The exterior masonry throughout appears to have appropriately spaced and inadequately caulked control joints in poor condition. Control joints are provided at lintel locations, at doors and windows, building corners, and wall offsets and are in poor condition. The Original Building does have sufficient expansion joints, and they are in poor condition. Cracking was observed in several areas on the exterior masonry. The 1988 Addition does have sufficient expansion joints, and they are in fair condition, and no cracking was observed on the exterior masonry. Exterior walls in the Original Building are inadequately insulated. Brick veneer masonry walls are not cavity walls. Exterior walls in the 1988 Addition are adequately insulated. Brick veneer masonry wall are cavity walls. On the Original Building, weep holes and vents are not provided or required. On the Gym Addition, weep holes are provided in sufficient quantity (at 24’’-48’’ on center) at the base of masonry cavity walls, and are in fair condition. Weep holes are not rope type weeps. Vents are not provided. The exterior masonry has not been cleaned and sealed in recent years, and shows evidence of efflorescence and mold in several locations. Architectural exterior accent materials consist of stone, which is in good condition, and mosaic tile, which is in poor condition. Exterior building fenestration in the Original Building represents 25% of the exterior surfaces, and fenestration in the 1988 Addition represents 3% of the exterior surfaces. Interior Corridor and demising walls are brick, concrete masonry units, and glazed block, project full height from floor to bottom of deck, and are in fair condition. Interior masonry appears to have adequately spaced and caulked control joints in fair condition. Interior soffits are of stud and gypsum board type construction, and in fair condition. The window sills are brick and aluminum, and are in fair condition. The exterior lintels are precast steel, and are rusting. Chimneys are in fair condition with minor cracking observed. Exterior soffits are of suspended exterior drywall type construction, and in poor condition. The school is provided with an uncovered, concrete conventional loading dock to facilitate the receipt of product, supplies, and foodstuffs, 245 square feet in size. The dock itself is in fair condition, and is equipped with bumper pads in fair condition.
Rating:
2 Needs Repair
Recommendations:
Provide tuckpointing in all areas of mortar deterioration as required in the Original Building. Provide masonry cleaning and sealing as required through the overall facility. Recaulk existing control joints at the Original Building. Prep and paint exposed steel lintels through the overall facility. Repair exterior soffits, stone accents, and mosaic tile where damage has occurred. Additional wall insulation is addressed in Item J.
Item
Cost
Unit
Whole BuildingOriginal Construction (1963)Gym Wing (1988)Sum Comments 42,740 ft² 7,187 ft² Tuckpointing: $5.25sq.ft. (Qty) 1,000 Required $5,250.00(wall surface) Exterior Masonry Cleaning: $1.50sq.ft. (Qty) 13,000 Required 11,000 Required $36,000.00(wall surface) Exterior Masonry Sealing: $1.00sq.ft. (Qty) 13,000 Required 11,000 Required $24,000.00(wall surface) Exterior Caulking: $5.50ln.ft. 200 Required $1,100.00(removing and replacing) Other: Paint steel lintels $5.00ln.ft. 100 Required 50 Required $750.00Prep and repaint steel lintels. Other: Repair and Paint Exterior Soffits $10.00sq.ft. (Qty) 100 Required 50 Required $1,500.00Repair damage to exterior soffits. Other: Repair Ceramic Tile $20.00sq.ft. (Qty) 500 Required $10,000.00Repair mosaic tile panels. Other: Repair stone trim $500.00per unit 5 Required $2,500.00Repair stone accents. Sum: $81,100.00 $50,350.00 $30,750.00
Brick to be Tuckpointed
Control Joint to be Caulked
Back to Assessment Summary
Facility Assessment
Page 17
Report Generated at 23 Dec 2015 10:42
Facility Assessment
I. Structure: Floors and Roofs Description:
The floor construction of the base floor of the Original Building and 1988 Addition is concrete slab on grade construction, and is in fair condition. There is no crawl space. The floor construction of the second floor of the Original Building is metal form deck on steel joist type construction, and is in fair condition. Ceiling to structural deck spaces are insufficient to accommodate HVAC, electrical, and plumbing scopes of work in required renovations. The roof construction of the Original Building is metal form deck on steel joist type construction, and is in fair condition. The roof construction of the 1988 Addition is metal form deck on steel joist type construction, and is in fair condition.
Rating:
1 Satisfactory
Recommendations:
Refer to Item A for funding of architectural soffits to accommodate HVAC, electrical, and plumbing scopes of work.
Item CostUnitWhole BuildingOriginal Construction (1963)Gym Wing (1988)SumComments 42,740 ft² 7,187 ft² Sum: $0.00 $0.00 $0.00
Typical Roof Deck
Typical Gymnasium Structure Back to Assessment Summary
Facility Assessment
Page 18
Report Generated at 23 Dec 2015 10:42
Facility Assessment
J. General Finishes Description:
The overall facility features conventionally partitioned Classrooms with carpet tile and vinyl type flooring, 2x4 ACT type ceilings, as well as painted CMU type wall finishes, and they are in good condition. The overall facility has Corridors with terrazzo, vinyl, and carpet tile type flooring, 2x4 ACT type ceilings, as well as brick and painted CMU type wall finishes, and they are in good condition. The overall facility has Restrooms with terrazzo type flooring, 2x4 ACT type ceilings, as well as painted CMU type wall finishes, and they are in fair condition. Toilet partitions are plastic, and are in good condition. The 1988 Addition has Corridors with terrazzo, vinyl, and carpet tile type flooring, 2x4 ACT type ceilings, as well as brick and painted CMU type wall finishes, and they are in good condition. Classroom casework in the overall facility is wood type construction with plastic laminate tops, is adequately provided, and in fair condition. The typical Classroom contains 8’ lineal feet of casework. Classrooms are provided adequate chalkboards, markerboards, tackboards which are in good condition. The Classroom storage cubbies, located in the Classrooms, are adequately provided, and in fair condition. The Art program is not equipped with a kiln. The facility is equipped with wood non-louvered interior doors that are partially recessed with proper ADA hardware and clearances, and in good condition. The Gymnasium space(s) have VCT type flooring, open type ceilings, as well as painted CMU type wall finishes, and they are in good condition. Gymnasium basketball backboards are electrically operated type, and are in good condition. The Media Center, has carpet tile type flooring, 2x4 ACT type ceilings, as well as painted CMU type wall finishes, and they are in good condition. Student Dining, has VCT type flooring, metal panel type ceilings, as well as painted CMU type wall finishes, and they are in fair condition. No stage is provided. Existing Gymnasium, Student Dining, Media Center, and Music spaces are inadequately provided with appropriate sound attenuation acoustical surface treatments. The existing Kitchen is full service, is undersized based on current enrollment, and the existing Kitchen equipment, installed in 1987-2005, is in fair/poor condition.
Rating:
3 Needs Replacement
Recommendations:
Provide complete replacement of finishes and casework due to condition and installation of systems outlined in Items (A / C / D / E / I / K / L / M / N / T / U / W). Provide for the replacement of kitchen equipment due to age. Provide additional wall insulation per Item H.
Item
Cost
Complete Replacement of Finishes and Casework (Elementary): Art Program Kiln: Additional Wall Insulation
$15.90sq.ft. (of entire building addition) $2,750.00each $6.00sq.ft. (Qty)
Total Kitchen Equipment Replacement: Sum:
Unit
Whole Building
Original Construction (1963) 42,740 ft² Required
Gym Wing (1988) 7,187 ft²
Sum
Required
$793,839.30(elementary, per building area, with removal of existing)
1 Required 42,740 Required
$190.00sq.ft. (Qty)
$2,750.00 $256,440.00(includes the furring out of the existing walls, insulation and abuse resistant GWB) $272,650.00(square footage based upon only existing area of food preparation, serving, kitchen storage areas and walk-ins. Includes demolition and removal of existing kitchen equipment)
1,435 Required
$1,325,679.30$1,211,406.00
Comments
$114,273.30
Kitchen
Hallway with Damaged Tile Back to Assessment Summary
Facility Assessment
Page 19
Report Generated at 23 Dec 2015 10:42
Facility Assessment
K. Interior Lighting Description:
The typical Classrooms in the overall facility are equipped with T-8 lay-in 2x4 fluorescent fixtures with multi-level switching. Classroom fixtures are in good condition, providing an average illumination of 66 FC, thus complying with the 50 FC recommended by the OSDM. The typical Corridors in the overall facility are equipped with T-8 lay-in 2x4 fluorescent fixtures with dual level switching. Corridor fixtures are in good condition, providing an average illumination of 22 FC, thus complying with the 20 FC recommended by the OSDM. The Primary Gymnasium spaces are equipped with pendant T-8 2x4 mount fluorescent fixture type lighting, in good condition, providing an average illumination of 50 FC, thus complying with the 50 ES FC recommended by the OSDM. The Media Center is equipped with lay-in 2x4 T-8 fluorescent fixture type lighting in good condition, providing an average illumination of 75 FC, thus complying with the 50 FC recommended by the OSDM. The Student Dining spaces are equipped with 1x4 surface mount T-8 fluorescent fixture type lighting with multi-level switching. Student Dining fixtures are in poor condition, providing an average illumination of 30 FC, which is less than the 50 FC recommended by the OSDM. The Kitchen spaces are equipped with 1x4 surface mount T-8 fluorescent fixture type lighting with single level switching. Kitchen fixtures are in good condition, providing an average illumination of 56 FC, which is less than the 75-80 FC recommended by the OSDM. The Service Areas in the overall facility are equipped with 1x4 suspended T-8 fluorescent fixture type lighting in good condition. The typical Administrative spaces in the overall facility are equipped with lay-in 2x4 T-8 fluorescent fixture type lighting in good condition, providing adequate illumination based on OSDM requirements. The overall lighting systems of the facility are not fully compliant with Ohio School Design Manual requirements due to inadequate lighting levels and lack of multi-level switching.
Rating:
3 Needs Replacement
Recommendations:
Provide complete replacement of lighting system due to lighting levels, lack of multi-level switching, installation of systems outlined in Item U.
Item
Cost Unit
Complete Building Lighting Replacement Sum:
$5.00sq.ft. (of entire building addition)
Whole Building
$249,635.00
Original Construction (1963) 42,740 ft² Required
Gym Wing (1988) 7,187 ft² Required
$213,700.00
$35,935.00
Corridor Lighting
Sum
Comments
$249,635.00Includes demo of existing fixtures
Gym Lighting Back to Assessment Summary
Facility Assessment
Page 20
Report Generated at 23 Dec 2015 10:42
Facility Assessment
L. Security Systems Description:
The overall facility contains a Security Command motion detector, CCTV, intrusion, and door contact type security system in good condition. Motion detectors are not adequately provided in main entries, central gathering areas, offices, main Corridors, and spaces where 6 or more computers are located. Exterior doors are equipped with door contacts. An automatic visitor control system is provided. Compliant color CCTV cameras are not provided at parking lots, central gathering areas, and main Corridors. CCTV is monitored in Administrative Area with the use of a TV. A compliant computer controlled access control system integrating alarms and video signals, with appropriate UPS backup, is not provided. The system is equipped with card readers. The security system is not adequately provided throughout, and the system is not compliant with Ohio School Design Manual guidelines. The exterior site lighting system is equipped with surface mounted high pressure sodium entry lights in fair condition. Pedestrian walkways are illuminated with high pressure sodium fixtures in fair condition. Parking and bus pick-up / drop off areas are illuminated by pole mounted high pressure sodium fixtures in fair condition. The exterior site lighting system provides inadequate illumination due to sparse placement of fixtures.
Rating:
3 Needs Replacement
Recommendations:
Provide new security system to meet Ohio School Design Manual guidelines.
Item
Cost Unit
Whole BuildingOriginal Construction (1963)Gym Wing (1988)Sum Comments 42,740 ft² 7,187 ft² Security System:$1.85sq.ft. (of entire building addition) Required Required $92,364.95(complete, area of building) Sum: $92,364.95 $79,069.00 $13,295.95
Door Security Contacts/Exit Signs/FA Pull Stations
Camera Monitor Back to Assessment Summary
Facility Assessment
Page 21
Report Generated at 23 Dec 2015 10:42
Facility Assessment
M. Emergency/Egress Lighting Description:
The overall facility is equipped with an emergency egress lighting system consisting of non-compliant plastic construction exit signs, as well as OSDM compliant red lettered, LED illuminated exit signs, and the system is in good condition. The facility is equipped with emergency egress floodlighting, and the system is in good condition. The system is provided with appropriate battery backup. The system is adequately provided throughout, and does not meet Ohio School Design Manual and Ohio Building Code requirements.
Rating:
3 Needs Replacement
Recommendations:
Provide new emergency / egress lighting system to meet Ohio School Design Manual and Ohio Building Code guidelines and in conjunction with work in Item U.
Item
Cost Unit
Whole BuildingOriginal Construction (1963)Gym Wing (1988)Sum Comments 42,740 ft² 7,187 ft² Emergency/Egress Lighting:$1.00sq.ft. (of entire building addition) Required Required $49,927.00(complete, area of building) Sum: $49,927.00 $42,740.00 $7,187.00
Exit Sign With Remote Heads
Battery Pack Back to Assessment Summary
Facility Assessment
Page 22
Report Generated at 23 Dec 2015 10:42
Facility Assessment
N. Fire Alarm Description:
The overall facility is equipped with a Simplex type fire alarm system, and is in good condition, consisting of manual pull stations, bells, and horn and strobe indicating devices. The system is automatic and is monitored by a third party. The system is equipped with sufficient audible horns and strobe indicating devices. The system is not equipped with sufficient smoke detectors or heat sensors. The system is not equipped with any flow switches or tamper switches. The system thus will not support future fire suppression systems. The system is adequately provided throughout, and does not have additional zone capabilities. The system is not fully compliant with Ohio Building Code, NFPA, and Ohio School Design Manual requirements.
Rating:
3 Needs Replacement
Recommendations:
Provide new fire alarm system to meet OBC, NFPA, and Ohio School Design Manual guidelines.
Item
Cost Unit
Fire Alarm System: Sum:
$1.50sq.ft. (of entire building addition)
Whole Building
$74,890.50
Original Construction (1963) 42,740 ft² Required
Gym Wing (1988) 7,187 ft² Required
$64,110.00
$10,780.50
Fire Alarm Horn Strobe
Sum
Comments
$74,890.50(complete new system, including removal of existing)
Gym Fire Alarm Equipment
Back to Assessment Summary
Facility Assessment
Page 23
Report Generated at 23 Dec 2015 10:42
Facility Assessment
O. Handicapped Access Description:
At the site, there is an accessible route provided from the public right-of-way, the accessible parking areas, and from the passenger unloading zone to the main entrance of the school. There is an accessible route connecting all or most areas of the site. The exterior entrances are not all ADA accessible due to existing site topography. Access from the parking and drop-off area to the building entries is compromised by steps or steep ramps. Adequate handicap parking is provided. Exterior doors are not equipped with ADA hardware. Building entrances should be equipped with one ADA power assist door, and none are provided. Playground layout and equipping are mostly compliant. On the interior of the building, space allowances and reach ranges are mostly compliant. There is an accessible route through the building which does not include protruding objects. Ground and floor surfaces are not compliant. Ramps and stairs do not meet all ADA requirements, and are insufficient due to railing heights. Elevation changes within the overall facility are facilitated by 2 non-compliant stairwells in fair condition, 1 compliant lift in good condition. This multistory building has a compliant elevator that accesses every floor and is in good condition. No Stage is provided. Interior doors are recessed, are not provided adequate clearances, and are provided with ADA-compliant hardware. 14 ADA-compliant toilets are required, and 2 are currently provided. 14 ADA-compliant Restroom lavatories are required, and 2 are currently provided. 2 ADA-compliant urinals are required, and 3 are currently provided. 8 ADA-compliant electric water coolers are required, and 4 are currently provided. Toilet partitions are plastic, and do not provide appropriate ADA clearances. ADA-compliant accessories are not adequately provided and mounted. Mirrors do not meet ADA requirements for mounting heights. Due to existing grade configuration, no Science Classroom considerations require evaluation. Health Clinic and Special Education Restrooms are not compliant with ADA requirements due to size of restrooms. ADA signage is not provided on both the interior and the exterior of the building.
Rating:
3 Needs Replacement
Recommendations:
Provide ADA-compliant signage, power assist door opener, ramps, electric water coolers, toilets, sinks, urinals, toilet partitions, toilet accessories in the overall facility to facilitate the school’s meeting of ADA requirements. Parking issues are corrected in Item P.
Item
Cost
Signage:
$0.20sq.ft. (of entire building addition) $3,000.00unit $3,800.00unit $1,500.00unit $1,000.00stall
Electric Water Coolers: Toilet/Urinals/Sinks: Toilet/Urinals/Sinks: Toilet Partitions: ADA Assist Door & Frame: Sum:
Unit
Whole Building
$7,500.00unit $108,585.40
Original Construction (1963) 42,740 ft² Required
Gym Wing (1988) 7,187 ft² Required
Sum
4 Required 12 Required 8 Required 14 Required
0 Required
1 Required
1 Required
$12,000.00(new double ADA) $45,600.00(new ADA) $12,000.00(replacement ADA) $14,000.00(ADA - grab bars, accessories included) $15,000.00(openers, electrical, patching, etc)
$99,648.00
$8,937.40
ADA-restroom
Comments
$9,985.40(per building area)
Steps at Front Sidewalk Back to Assessment Summary
Facility Assessment
Page 24
Report Generated at 23 Dec 2015 10:42
Facility Assessment
P. Site Condition Description:
The school is located on two acres of a larger overall shared site that is moderately sloped site and located in a suburban residential setting with moderate tree and shrub type landscaping. Outbuildings include a district vehicle garage. There are no apparent problems with erosion or ponding. The site is bordered by lightly traveled city streets. Multiple entrances onto the site do not facilitate proper separation of bus and other vehicular traffic, and one way bus traffic is not provided. There is a curbside bus loading and unloading zone in front of the school, which is not separated from other vehicular traffic. A bus loop is not provided for student loading and unloading. Staff and visitor parking is facilitated by a multiple asphalt parking lots in fair condition, containing 55 with 2 accessible staff parking places and 17 with 4 accessible visitor parking spaces, which provides adequate parking for staff members, visitors, and the disabled. The site and parking lot drainage design, consisting of sheet drainage, catch basins, storm sewers, provides adequate evacuation of storm water, and no problems with parking lot ponding were observed. Concrete curbs in fair condition are appropriately placed. Concrete sidewalks are properly sloped, are located to provide a logical flow of pedestrian traffic, and are in fair condition. Trash pick-up and service drive pavement is not heavy duty and is in fair condition, and is not equipped with a concrete pad area for dumpsters. The loading dock is in fair condition. There are steps and three handrails at the east side of the building from sidewalk at the bus drop-off area at the front of the school that are in fair condition. There is a concrete courtyard at the east side of the building with a 24’’ perimeter wall that is in fair condition. The courtyard has seven raised planting beds and there is an exterior hose bib on the east wall of the facility. The wood retaining wall at the west parking lot is overturning and is in poor condition. There is adequate fencing separating the west parking lot and the playgrounds and playing fields, and is in fair condition. The playground equipment is primarily constructed of coated steel and high density and is in fair condition. Playground equipment is placed to provide compliant fall zones, and on a compliant other soft surface of sufficient, with a basketball court being provided on an asphalt surface in fair condition. The playground area is equipped with benches in fair condition. The athletic facilities are comprised of hard surface basketball courts, soccer area, hockey area, and a grass soccer field, and are in fair condition. Site features are suitable for outdoor instruction.
Rating:
3 Needs Replacement
Recommendations:
Provide bus loop for student loading and unloading. Replace wood retaining wall at the west parking lot location due to structural deterioration. Provide a concrete pad for dumpsters. It is recommended to replace playground equipment to more ADA-compliant play structures.
Item
Cost
Playground Equipment:
Unit
$1.50sq.ft. (Qty)
Bus Drop-Off for Elementary
$110.00per student
Provide Concrete Dumpster Pad: Base Sitework Allowance for Unforeseen Circumstances
$2,400.00each $50,000.00allowance
Sitework Allowance for Unforeseen Circumstances for buildings between 0 SF and 100,000 SF Other: Replace retaining wall Sum:
$1.50sq.ft. (of entire building addition) $150.00ln.ft.
Whole Building
Original Construction (1963) 42,740 ft² 42,740 Required
Gym Wing (1988) 7,187 ft²
Sum
7,187 Required
$74,890.50(up to $100,000, per sq.ft. of school)
480 Required
1 Required Required
Required
250 Required $292,481.00 $270,920.00
Required
Comments
$52,800.00(Number of students should be rounded up to the nearest 100. $5500 per bus; 40 students per bus; 80% of elementary school students riding) $2,400.00(for two dumpsters) $50,000.00Include this and one of the next two. (Applies for whole building, so only one addition should have this item) $74,890.50Include this one or the next. (Each addition should have this item) $37,500.00Replace retaining wall.
$21,561.00
Typical Playground
Retaining Wall to be Replaced Back to Assessment Summary
Facility Assessment
Page 25
Report Generated at 23 Dec 2015 10:42
Facility Assessment
Q. Sewage System Description:
The sanitary sewer system is tied in to the city system, and is in good condition. No significant system deficiencies were reported by the school district or noted during the physical assessment.
Rating:
1 Satisfactory
Recommendations:
Existing conditions require no renovation or replacement at the present time.
Item CostUnitWhole BuildingOriginal Construction (1963)Gym Wing (1988)SumComments 42,740 ft² 7,187 ft² Sum: $0.00 $0.00 $0.00
Kitchen Sink Waste
Kitchen Sink Waste Back to Assessment Summary
Facility Assessment
Page 26
Report Generated at 23 Dec 2015 10:42
Facility Assessment
R. Water Supply Description:
The domestic water supply system is tied in to the city system, features 3’’ service and 2’’ water meter, and is in fair condition. The District was not able to provide water supply flow test data. The existing domestic water service appears to meet the facility’s current needs. The facility is not equipped with an automated fire suppression system, and the existing water supply will not provide adequate support for a future system. The domestic water service is not equipped with a water booster pump. The system provides adequate pressure for the future needs of the school.
Rating:
1 Satisfactory
Recommendations:
Provide a new city water supply line of adequate capacity to support the existing needs of the facility, as well as a future automated fire suppression system. Funding provided in Item U.
Item CostUnitWhole BuildingOriginal Construction (1963)Gym Wing (1988)SumComments 42,740 ft² 7,187 ft² Sum: $0.00 $0.00 $0.00
Water Meter
Water Main Back to Assessment Summary
Facility Assessment
Page 27
Report Generated at 23 Dec 2015 10:42
Facility Assessment
S. Exterior Doors Description:
Typical exterior doors in the 1963 Original Construction are hollow metal type construction, installed on hollow metal frames, and in fair condition. Typical exterior doors feature single wired glass vision panels, and appropriate hardware. Typical exterior doors in the 1988 Gym Addition are aluminum type construction, installed on aluminum frames, and in good condition. Typical exterior doors feature no vision panels, and appropriate hardware. Entrance doors in the 1963 Original Facility are hollow metal type construction, installed on aluminum frames, and in fair condition and feature single glazed wired glass vision panels, transoms, and appropriate hardware. Entrance doors in the 1988 Gym Addition are aluminum type construction, installed on aluminum frames, and in good condition and feature double glazed tempered glass, transoms, side-lights and appropriate hardware. The facility is equipped with one roof access door, which is in fair condition. There are no overhead doors in the facility.
Rating:
3 Needs Replacement
Recommendations:
Replace all exterior and entrance doors in the Original Building to comply with Ohio Building Code, ADA, and Ohio School Design Manual guidelines.
Item
Cost
Unit
Whole BuildingOriginal Construction (1963)Gym Wing (1988)Sum Comments 42,740 ft² 7,187 ft² Door Leaf/Frame and Hardware:$2,000.00per leaf 17 Required $34,000.00(includes removal of existing) Sum: $34,000.00 $34,000.00 $0.00
Original Building Entrance Doors
1988 Addition Entrance Doors
Back to Assessment Summary
Facility Assessment
Page 28
Report Generated at 23 Dec 2015 10:42
Facility Assessment
T. Hazardous Material Description:
The School District provided the AHERA Three Year Reinspection Reports, prepared by Gandee & Associates, Inc. and dated May 2014, documenting known and assumed locations of asbestos and other hazardous materials. The district did not provide documentation of any abatement projects since that time. In the 1963 Original Construction , Resiliant Floor Covering and Mastic containing hazardous materials are reported and with no indication of condition. These materials were described in the report to be in non-friable condition with no reported damage. No estimated quantity was given in the report. Quatities added to the assessment are assumed based on existing square feet in the areas listed. Pipe Fitting Insulation containing hazardous materials are reported to be in good condition, friable, with light damage. (368ct) Due to the construction date, there is potential for lead based paint in the Original Construction. Fluorescent lighting will require special disposal.
Rating:
3 Needs Replacement
Recommendations:
Remove all hazardous materials, inclusive of asbestos-containing materials in the overall facility, as noted in the attached AHERA Three Year Reinspection Report. Provide for the testing of paint that has the potential of being lead-based. Provide for disposal of fluorescent lighting.
Item
Cost
Unit
Whole BuildingOriginal Construction (1963)Gym Wing (1988)Sum Comments 42,740 ft² 7,187 ft² Environmental Hazards Form EEHA Form EEHA Form — Fluorescent Lamps & Ballasts Recycling/Incineration $0.10sq.ft. (Qty) 42,740 Required 7,187 Required $4,992.70 Pipe Fitting Insulation Removal $20.00each 368 Required 0 Required $7,360.00 Resilient Flooring Removal, Including Mastic $3.00sq.ft. (Qty) 19,000 Required 0 Required $57,000.00See J Sum: $69,352.70 $68,634.00 $718.70
Back to Assessment Summary
Facility Assessment
Page 29
Report Generated at 23 Dec 2015 10:42
Facility Assessment
U. Life Safety Description:
The overall facility is not equipped with an automated fire suppression system. Exit Corridors are situated such that dead-end Corridors are not present. The facility features 2 interior stair towers, which are not protected by a compliant two hour fire enclosure. The facility features 0 exterior stairways providing egress from intermediate floors. Guardrails do not meet the 4’’ ball test and do not extend past the top and bottom stair risers as required by the Ohio Building Code. The 1988 Addition is equipped with a compliant automated fire suppression system in fair condition. The Kitchen hood is in poor condition, and is equipped with the required UL 300 compliant wet chemical fire suppression system. The cooking equipment is interlocked to shut down in the event of discharge of the fire suppression system. The facility is not equipped with an emergency generator. The existing water supply is provided by a tie-in to the city system, and is insufficient to meet the future fire suppression needs of the school. Rooms with a capacity greater than 50 occupants are equipped with adequate egress.
Rating:
3 Needs Replacement
Recommendations:
Provide new automated fire suppression system to meet Ohio School Design Manual guidelines. Provide increased water service of a capacity sufficient to support the fire suppression system, funding included in fire suppression funding. Provide new emergency generator, with funding provided via complete replacement of electrical system in Item D. Provide new Kitchen hood with a UL 300 compliant wet chemical fire suppression system. Provide new handrails to meet the requirements of the Ohio Building Code.
Item
Cost
Sprinkler / Fire Suppression System:
$3.20sq.ft. (Qty) $5,000.00per level
Interior Stairwell Closure: Handrails: Retrofit existing kitchen hood with Fire suppression system Sum:
Unit
$5,000.00level $6,500.00per hood
Whole Building
Original Construction (1963) 42,740 ft² 42,740 Required 4 Required 4 Required 1 Required
$206,260.00 $183,268.00
Kitchen Hood
Gym Wing Sum Comments (1988) 7,187 ft² 7,185 Required $159,760.00(includes increase of service piping, if required) $20,000.00(includes associated doors, door frames and hardware) $20,000.00 $6,500.00 $22,992.00
stairs Back to Assessment Summary
Facility Assessment
Page 30
Report Generated at 23 Dec 2015 10:42
Facility Assessment
V. Loose Furnishings Description:
The typical Classroom furniture is mismatched, and in generally fair condition, consisting of student desks & chairs, teacher desks & chairs, desk height file cabinets, reading tables, computer workstations, bookcases, wastebaskets, and other. The facility’s furniture and loose equipment were evaluated in item 6.17 in the CEFPI section of this report, and on a scale of 1 to 10 the overall facility received a rating of 4 due to observed conditions, and due to the fact that it lacks some of the Design Manual required elements.
Rating:
3 Needs Replacement
Recommendations:
Provide for replacement of outdated or inadequate furnishings.
Item
Cost Unit
Whole BuildingOriginal Construction (1963)Gym Wing (1988)Sum Comments 42,740 ft² 7,187 ft² CEFPI Rating 4 to 5$4.00sq.ft. (of entire building addition) Required Required $199,708.00 Sum: $199,708.00 $170,960.00 $28,748.00
library
classroom Back to Assessment Summary
Facility Assessment
Page 31
Report Generated at 23 Dec 2015 10:42
Facility Assessment
W. Technology Description:
The typical Classroom is equipped with the required four technology data ports for student use, one data port for teacher use, one voice port with a digitally based phone system, one cable port and monitor, and a 2-way PA system that can be initiated by either party to meet Ohio School Design Manual requirements. The facility is equipped with a centralized clock system. Specialized electrical / sound system requirements of Gymnasium, Stage, Student Dining, and Music spaces are inadequately provided, and in good condition. OSDM-compliant computer network infrastructure is provided. The facility does contain a media distribution center, and provides Computer Labs for use by students.
Rating:
3 Needs Replacement
Recommendations:
Provide complete replacement of technology systems to meet Ohio School Design Manual requirements, and to sustain the capacity to keep pace with technological development.
Item
Cost
Unit
Whole BuildingOriginal Construction (1963)Gym Wing (1988)Sum Comments 42,740 ft² 7,187 ft² ES portion of building with total SF < 50,000$13.18sq.ft. (Qty) 42,740 Required 7,187 Required $658,037.86 Sum: $658,037.86 $563,313.20 $94,724.66
Smartboard/Projector
Smartboard Back to Assessment Summary
Facility Assessment
Page 32
Report Generated at 23 Dec 2015 10:42
Facility Assessment
X. Construction Contingency / Non-Construction Cost Renovation Costs (A-W) 7.00%
$6,527,267.06
Construction Contingency
Subtotal 16.29%
$456,908.69 $6,984,175.75
Non-Construction Costs
Total Project
$1,137,722.23 $8,121,897.98
Construction Contingency
$456,908.69
Non-Construction Costs
$1,137,722.23
Total for X.
$1,594,630.92
Non-Construction Costs Breakdown Land Survey
0.03%
$2,095.25
Soil Borings / Phase I Envir. Report
0.10%
$6,984.18
Agency Approval Fees (Bldg. Code)
0.25%
$17,460.44
Construction Testing
0.40%
$27,936.70
Printing - Bid Documents
0.15%
$10,476.26
Advertising for Bids
0.02%
$1,396.84
Builder’s Risk Insurance
0.12%
$8,381.01
Design Professional’s Compensation
7.50%
$523,813.18
CM Compensation
6.00%
$419,050.55
Commissioning
0.60%
$41,905.05
Non-Construction Contingency (includes partnering and mediation services)
1.12%
$78,222.77
16.29%
$1,137,722.23
Total Non-Construction Costs Back to Assessment Summary
Facility Assessment
Page 33
Report Generated at 23 Dec 2015 10:42
School Facility Appraisal
Name of Appraiser
Holly Grambort
Date of Appraisal
Building Name
Evening Street Elementary
Street Address
885 Evening St
City/Town, State, Zip Code
Worthington, OH 43085
Telephone Number(s)
(614) 450-4400
School District
Worthington City
Setting:
Suburban
2015-09-23
Site-Acreage
2.00
Building Square Footage
49,927
Grades Housed
K-6
Student Capacity
576
Number of Teaching Stations
25
Number of Floors
1
Student Enrollment
579
Dates of Construction
1963,1988
Energy Sources:
Fuel Oil
Gas
Electric
Solar
Air Conditioning:
Roof Top
Windows Units
Central
Room Units
Heating:
Central
Roof Top
Individual Unit
Forced Air
Hot Water
Steam
Type of Construction
Exterior Surfacing
Floor Construction
Load bearing masonry
Brick
Wood Joists
Steel frame
Stucco
Steel Joists
Concrete frame
Metal
Slab on grade
Wood
Wood
Structural slab
Steel Joists
Stone
Back to Assessment Summary
School Facility Appraisal
Page 34
Report Generated at 23 Dec 2015 10:42
CEFPI Ratings Sheet
1.0 The School Site School Facility Appraisal
Points Allocated
1.1
Site is large enough to meet educational needs as defined by state and local requirements
Points
25
5
20
16
10
8
10
4
10
8
The site is 2 acres compared to 16 acres required by the OSDM.
1.2
Site is easily accessible and conveniently located for the present and future population The School is centrally located within the School District, and is easily accessible.
1.3
Location is removed from undesirable business, industry, traffic, and natural hazards The site is adjacent to residential uses, which is suitable for educational instruction.
1.4
Site is well landscaped and developed to meet educational needs The site has limited landscaping, which does not enhance the property or emphasize the building entrance.
1.5
ES
Well equipped playgrounds are separated from streets and parking areas
MS
Well equipped athletic and intermural areas are separated from streets and parking
HS
Well equipped athletic areas are adequate with sufficient solid-surface parking
Playground areas consist of metal and composite plastic type play equipment, which is in good condition, and is located on wood fiber mulch which is an approved soft surface material. Play equipment is not ADA accessible, and includes an accessible route to equipment. Fencing is provided to separate vehicular traffic from pedestrians.
1.6
Topography is varied enough to provide desirable appearance and without steep inclines
5
4
The site is gently sloped to provide positive drainage across the site. A flat area is provided to accommodate buildings, perimeter walks, vehicular circulation, parking areas, outdoor play areas, and physical education spaces, and is desirable.
1.7
Site has stable, well drained soil free of erosion
5
4
5
3
5
4
Soils appear to be stable and well drained, and no erosion was observed.
1.8
Site is suitable for special instructional needs, e.g., outdoor learning The site has limited development to accommodate outdoor learning, including benches and picnic tables to facilitate instruction.
1.9
Pedestrian services include adequate sidewalk with designated crosswalks, curb cuts, and correct slopes
Sidewalks are adequately provided to accommodate safe pedestrian circulation including designated crosswalks, curb cuts, and correct slopes.
1.10
ES/MS
Sufficient on-site, solid surface parking for faculty and staff is provided
HS
Sufficient on-site, solid surface parking is provided for faculty, students, staff and community
5
4
Adequate parking is provided for faculty, staff, community and student parking, and is located on asphalt pavement in fair condition.
TOTAL - The School Site
CEFPI Ratings Sheet
100
Page 35
60
Report Generated at 23 Dec 2015 10:42
Back to Assessment Summary
CEFPI Ratings Sheet
Page 36
Report Generated at 23 Dec 2015 10:42
CEFPI Ratings Sheet
2.0 Structural and Mechanical Features School Facility Appraisal
Points Allocated
Structural
2.1
Structure meets all barrier-free requirements both externally and internally
Points
15
2
15
4
10
9
10
5
10
8
10
8
10
4
10
4
Entire building is not ADA-compliant.
2.2
Roofs appear sound, have positive drainage, and are weather tight The roofs over the entire building are in good condition but require replacement due to age of systems.
2.3
Foundations are strong and stable with no observable cracks Foundations are in good condition with no observable cracks.
2.4
Exterior and interior walls have sufficient expansion joints and are free of deterioration Exterior and interior walls are in fair condition, have sufficient control and expansion joints which are starting to show signs of deterioration.
2.5
Entrances and exits are located so as to permit efficient student traffic flow Exits are properly located to allow safe egress from the building.
2.6
Building ’’envelope’’ generally provides for energy conservation (see criteria) Building envelope meets minimum energy requirements.
2.7
Structure is free of friable asbestos and toxic materials The building is reported to contain asbestos and other hazardous materials.
2.8
Interior walls permit sufficient flexibility for a variety of class sizes Interior walls throughout the facility are fixed walls and are not flexible.
Points Allocated
Mechanical/Electrical
2.9
Adequate light sources are well maintained, and properly placed and are not subject to overheating
Points
15
12
15
14
15
8
Fixtures are properly maintained and placed. Fixtures are not subject to overheating.
2.10
Internal water supply is adequate with sufficient pressure to meet health and safety requirements Water pressure was measured at 70 PSI.
2.11
Each teaching/learning area has adequate convenient wall outlets, phone and computer cabling for technology applications
Computer technology cabling is adeqautley installed in teaching/learning areas. There is an inadequate amount of wall outlets in teaching/learning spaces.
2.12
Electrical controls are safely protected with disconnect switches easily accessible
CEFPI Ratings Sheet
Page 37
10
5
Report Generated at 23 Dec 2015 10:42
Electrical controls are safely protected but are difficult to access. Storage materials are kept infront of electrical equipment.
2.13
Drinking fountains are adequate in number and placement, and are properly maintained including provisions for the disabled
10
4
Drinking fountains are not adequate in number and placement, and do not meet ADA requirements. Drinking fountains are properly maintained.
2.14
Number and size of restrooms meet requirements
10
2
10
8
10
4
10
8
5
4
The number and size of Restrooms do not meet requirements.
2.15
Drainage systems are properly maintained and meet requirements The roof drains are adequate in number and placement. There are floor drains in the mechanical rooms.
2.16
Fire alarms, smoke detectors, and sprinkler systems are properly maintained and meet requirements Fire alarms devices are properly placed, there is an inadeqaute amount of smoke detectors.
2.17
Intercommunication system consists of a central unit that allows dependable two-way communication between the office and instructional areas A two way communication system with a central office and teaching/learning stations allows for intercommunication.
2.18
Exterior water supply is sufficient and available for normal usage Hose bibs are provided on all sides of the building.
TOTAL - Structural and Mechanical Features
200
113
Back to Assessment Summary
CEFPI Ratings Sheet
Page 38
Report Generated at 23 Dec 2015 10:42
CEFPI Ratings Sheet
3.0 Plant Maintainability School Facility Appraisal
Points Allocated
3.1
Windows, doors, and walls are of material and finish requiring minimum maintenance
Points
15
9
15
6
Exterior materials for walls require minimum maintenance. Materials and finishes for doors and windows require some maintenance.
3.2
Floor surfaces throughout the building require minimum care
Flooring throughout the facility consists of VCT, terrazzo which is not well maintained throughout the facility. Wood flooring is not easily maintained in the Classrooms.
3.3
Ceilings and walls throughout the building, including service areas, are easily cleaned and resistant to stain
10
6
Acoustical tile ceilings are not easily cleaned or resistant to stain. Painted block is easily cleaned and resistant to stain. Glazed block is easily cleaned and resistant to stain.
3.4
Built-in equipment is designed and constructed for ease of maintenance
10
4
10
4
10
6
10
5
10
5
10
6
Casework consists of miscellaneous wood and metal shelving units in poor condition.
3.5
Finishes and hardware, with compatible keying system, are of durable quality Due to multiple additions throughout the facility, keying systems are not compatible and are worn.
3.6
Restroom fixtures are wall mounted and of quality finish Fixtures are floor and wall mounted and are of fair quality.
3.7
Adequate custodial storage space with water and drain is accessible throughout the building Custodial storage space is adequately located throughout the facility, including provisions for water and drains.
3.8
Adequate electrical outlets and power, to permit routine cleaning, are available in every area Corridor and teaching/learning areas are equipped with an inadequate amount of receptacles.
3.9
Outdoor light fixtures, electrical outlets, equipment, and other fixtures are accessible for repair and replacement Outdoor light fixtures are easily accessible. Exterior outlets are sparcely placed.
TOTAL - Plant Maintainability
100
51
Back to Assessment Summary
CEFPI Ratings Sheet
Page 39
Report Generated at 23 Dec 2015 10:42
CEFPI Ratings Sheet
4.0 Building Safety and Security School Facility Appraisal
Site Safety
4.1
Points Allocated
Student loading areas are segregated from other vehicular traffic and pedestrian walkways
Points
15
6
10
8
5
4
5
2
5
4
Student loading is not separated from other vehicular traffic.
4.2
Walkways, both on and offsite, are available for safety of pedestrians Walkways are adequately provided both on and off-site for pedestrian safety.
4.3
Access streets have sufficient signals and signs to permit safe entrance to and exit from school area School signs and signals are located as required on adjacent access streets.
4.4
Vehicular entrances and exits permit safe traffic flow Buses and other vehicular traffic use the same entrance and exit points to the site, which do not provide safe vehicular traffic flow.
4.5
ES
Playground equipment is free from hazard
MS
Location and types of intramural equipment are free from hazard
HS
Athletic field equipment is properly located and is free from hazard
Playground equipment consists of plastic coated steel and high density plastic type equipment in good condition, appears to be free from hazard, and is located on an approved soft surface material to a sufficient depth.
Building Safety
4.6
Points Allocated
The heating unit(s) is located away from student occupied areas
Points
20
7
15
6
10
6
10
8
10
8
10
6
The building has unit ventilators in the classrooms.
4.7
Multi-story buildings have at least two stairways for student egress The building does have 2 stairways, which are enclosed, and are not ADA and OBC compliant.
4.8
Exterior doors open outward and are equipped with panic hardware Exterior doors open in the direction of travel and are equipped with panic hardware.
4.9
Emergency lighting is provided throughout the entire building with exit signs on separate electrical circuits Emergency lighting is powered via battery packs and are adeqautely placed.
4.10
Classroom doors are recessed and open outward Classroom doors are adequately recessed with proper ADA clearances, and open outward.
4.11
Building security systems are provided to assure uninterrupted operation of the educational program
CEFPI Ratings Sheet
Page 40
Report Generated at 23 Dec 2015 10:42
Security system with door sensors and intrusion detection is installed, however the system lacks cameras in corridors, gathering areas and in areas with 6 or more computers.
4.12
Flooring (including ramps and stairways) is maintained in a non-slip condition
5
4
5
4
5
3
5
4
5
4
Terrazzo and VCT flooring have been well maintained throughout the facility.
4.13
Stair risers (interior and exterior) do not exceed 6 1/2 inches and range in number from 3 - 16 Stair treads and risers are properly designed and meet requirements.
4.14
Glass is properly located and protected with wire or safety material to prevent accidental student injury Glass at door transoms and sidelights is provided with wire mesh for safety.
4.15
Fixed Projections in the traffic areas do not extend more than eight inches from the corridor wall Water coolers have been recessed in the Corridor wall.
4.16
Traffic areas terminate at an exit or a stairway leading to an egress
Exits are properly located to allow safe egress from the building. Stairways empty to the exterior, or adjacent to a Corridor leading to the exterior. There are no dead-end Corridors in the building.
Emergency Safety
4.17
Points Allocated
Adequate fire safety equipment is properly located
Points
15
12
15
12
15
12
15
12
Fire safety equipment is properly located.
4.18
There are at least two independent exits from any point in the building Multiple exits are provided from Corridors throughout the facility.
4.19
Fire-resistant materials are used throughout the structure The structure is a masonry load bearing system with steel joist and concrete deck. Interior walls are masonry.
4.20
Automatic and manual emergency alarm system with a distinctive sound and flashing light is provided An automatic and manual fire alarm system is in place.
TOTAL - Building Safety and Security
200
132
Back to Assessment Summary
CEFPI Ratings Sheet
Page 41
Report Generated at 23 Dec 2015 10:42
CEFPI Ratings Sheet
5.0 Educational Adequacy School Facility Appraisal
Academic Learning Space
5.1
Points Allocated
Size of academic learning areas meets desirable standards
Points
25
15
15
9
10
8
10
4
10
4
10
4
The average Classroom is 870 SF compared to 900 SF required by the OSDM.
5.2
Classroom space permits arrangements for small group activity Undersized Classrooms do not allow sufficient space for effective small group activities.
5.3
Location of academic learning areas is near related educational activities and away from disruptive noise The Gymnasium and Music program are properly isolated from the academic learning areas to reduce distractions.
5.4
Personal space in the classroom away from group instruction allows privacy time for individual students Undersized Classrooms do not permit privacy time for individual students.
5.5
Storage for student materials is adequate Coat hooks and shelving, located in the Classroom, are inadequately provided for student storage.
5.6
Storage for teacher materials is adequate Miscellaneous wood and metal shelving units are inadequately provided for teacher storage.
Special Learning Space
5.7
Points Allocated
Size of special learning area(s) meets standards
Points
15
0
10
0
10
2
5
4
There are no Special Learning areas in the facility.
5.8
Design of specialized learning area(s) is compatible with instructional need There are no Special Learning areas in the facility.
5.9
Library/Resource/Media Center provides appropriate and attractive space The Media Center is not visually appealing and does not provide natural light.
5.10
Gymnasium (or covered P.E. area) adequately serves physical education instruction
The Gymnasium is 4,310 SF compared to ~4,000 SF recommended in the OSDM. (ES) The Gymnasium space is adequately sized and equipped for physical education instruction.
5.11
ES
Pre-kindergarten and kindergarten space is appropriate for age of students and nature of instruction
MS/HS
Science program is provided sufficient space and equipment
CEFPI Ratings Sheet
Page 42
10
8
Report Generated at 23 Dec 2015 10:42
Pre-K and Kindergarten spaces are adequate for age of students served.
5.12
Music Program is provided adequate sound treated space
5
2
The Music Room is 939SF compared to 1,800-3,000 recommended in the OSDM. Music instruction is provided in a standard Classroom without any sound treatment.
5.13
Space for art is appropriate for special instruction, supplies, and equipment
5
2
The Art Room is 939 SF compared to 1,200 SF recommended in the OSDM. The Art Room is appropriately designed for instruction and includes sufficient space for storage of supplies and equipment. The Art Room is undersized and does not provide sufficient space for storage of supplies and equipment.
School Facility Appraisal
5.14
Points Allocated
Space for technology education permits use of state-of-the-art equipment
Points
5
0
5
0
5
1
The facility is not provided with Computer Labs for student use.
5.15
Space for small groups and remedial instruction is provided adjacent to classrooms No spaces have been provided adjacent to Classrooms for small groups or remedial instruction.
5.16
Storage for student and teacher material is adequate Storage for teachers and students has not been adequately provided throughout the facility.
Support Space
5.17
Points Allocated
Teacher’s lounge and work areas reflect teachers as professionals
10
Points
2
The Teacher’s Lounge is 373 SF compared to 450-900 SF, for 8-24 staff, recommended in the OSDM. The Teacher’s Lounge does not reflect a professional environment. The Teacher’s Lounge does reflect a professional environment and includes adequate work space for preparation of teacher materials. Limited work space is provided for preparation of teacher materials.
5.18
Cafeteria/Kitchen is attractive with sufficient space for seating/dining, delivery, storage, and food preparation
10
2
The Student Dining space is 2,759 SF compared to 3,000 SF recommended in the OSDM. The Kitchen space is 1060 SF compared to 2016 SF recommended in the OSDM.
5.19
Administrative offices provided are consistent in appearance and function with the maturity of the students served
5
2
5
0
5
2
Administrative Offices are not adequately provided for Elementary School students.
5.20
Counselor’s office insures privacy and sufficient storage There is no separate space provided for a Councelor’s office.
5.21
Clinic is near administrative offices and is equipped to meet requirements
The Clinic is 221 SF compared to 370 SF recommended in the OSDM. The Clinic is located within the Administrative Offices and is provided with required equipment.
5.22
Suitable reception space is available for students, teachers, and visitors
5
2
There is a very small area for reception in the front office.
CEFPI Ratings Sheet
Page 43
Report Generated at 23 Dec 2015 10:42
5.23
Administrative personnel are provided sufficient work space and privacy
5
1
Administrative offices are not adequate.
TOTAL - Educational Adequacy
200
74
Back to Assessment Summary
CEFPI Ratings Sheet
Page 44
Report Generated at 23 Dec 2015 10:42
CEFPI Ratings Sheet
6.0 Environment for Education School Facility Appraisal
Exterior Environment
6.1
Points Allocated
Overall design is aesthetically pleasing to age of students
15
Points
9
The building is a modern design with minimal detailing consistent with similar facilities of the time of the original construction, which is dated and only marginally aesthetically pleasing.
6.2
Site and building are well landscaped
10
6
10
8
10
6
The site has limited landscaping, which does not enhance the property or emphasize the building entrance.
6.3
Exterior noise and poor environment do not disrupt learning The site is adjacent to residential uses, and there are no undesirable features adjacent to the school site.
6.4
Entrances and walkways are sheltered from sun and inclement weather
The main entrance to the School is partially sheltered. Exits are not sheltered from sun and inclement weather. On-site walkways to accessory buildings are not covered.
6.5
Building materials provide attractive color and texture
5
4
Exterior building materials consist of brick, stone, and concrete block, which do provide an attractive color and texture.
Interior Environment
6.6
Points Allocated
Color schemes, building materials, and decor provide an impetus to learning
20
Points
14
The color palette is comprised of achromatic hues. School colors are not reflected in the athletic areas. The use of repeated colors and materials gives the building some unity and a sense of consistency.
6.7
Year around comfortable temperature and humidity are provided throughout the building
15
14
15
7
15
7
15
9
10
6
The building has a central air conditioning system.
6.8
Ventilating system provides adequate quiet circulation of clean air and meets 15cfm VBC requirement It does not provide the minimum 15 CFM ventilation as required by the OBCMC.
6.9
Lighting system provides proper intensity, diffusion, and distribution of illumination The lighting system is not adequate for proper illumination.
6.10
Drinking fountains and restroom facilities are conveniently located Drinking fountains and Restroom facilities are somewhat conveniently located.
6.11
Communication among students is enhanced by commons area(s) for socialization
There are areas for students to gather in the Student Dining area and Gymnasium, as well as a very small gathering area at the entrance to the school.
CEFPI Ratings Sheet
Page 45
Report Generated at 23 Dec 2015 10:42
6.12
Traffic flow is aided by appropriate foyers and corridors
10
8
10
6
Corridors and Foyers are adequately designed for efficient traffic flow.
6.13
Areas for students to interact are suitable to the age group
There are areas for students to gather in the Student Dining area and Gymnasium, as well as a very small gathering area at the entrance to the school.
6.14
Large group areas are designed for effective management of students
10
8
10
6
10
4
10
4
The Gymnasium is adequately designed to manage large groups of students.
6.15
Acoustical treatment of ceilings, walls, and floors provides effective sound control Limited consideration has been given to acoustical treatment of Classrooms and Corridors.
6.16
Window design contributes to a pleasant environment The windows are not designed well, and do not contribute to a pleasant environment.
6.17
Furniture and equipment provide a pleasing atmosphere Classroom furniture is mismatched and in fair to poor condition.
TOTAL - Environment for Education
200
126
Back to Assessment Summary
CEFPI Ratings Sheet
Page 46
Report Generated at 23 Dec 2015 10:42
LEED Observation Notes School District:
Worthington City
County:
Franklin
School District IRN:
45138
Building:
Evening Street Elementary
Building IRN:
10868
Sustainable Sites Construction process can have a harmful effect on local ecology, especially when buildings are build on productive agricultural, wildlife or open areas. Several measures can be take however to prevent the impact on undeveloped lands or to improve previously contaminated sites. Appropriate location reduces the need for private transportation and helps to prevent an increase in air pollution. Developing buildings in urban areas and on brownfield sites instead of greenfield locations has economical and environmental benefits. Controlling stormwater runoff and erosion can prevent the worsening of water quality in receiving bodies of water and the impact on aquatic life. Once the building is constructed, it’s important to decrease heat island effects and reduce the light pollution on the site. (source: LEED Reference Guide, 2001:9) A major renovation to the school may be able to attain points in several site-related areas. Alternative Transportation points may be possible with the addition of parking areas designated for low-emission vehicles and car pools. Bike racks are provided and changing rooms could be added. Other transportation credits are unlikely to be achieved due to the schools relatively suburban location. A reduction in impervious paving, and use of alternative paving materials could aid in achieving Stormwater Design and Heat Island Effect Nonroof points. The school has a light colored, and therefore light-reflective, high-albedo roof material which could qualify for Heat Island Effect Roof points. Light Pollution Reduction could be achieved with updates to the site lighting. Water Efficiency In the US ca. 340 billion gallons of fresh water are withdrawn daily from surface sources, 65% of which is discharged later after use. Water is also withdrawn from underground aquifers The excessive usage of water results in the current water deficit, estimated at 3,700 billion gallons. Water efficiency measures in commercial buildings can reduce water usage by at least 30%. Low-flow fixtures, sensors or using non potable water for landscape irrigation, toilet flushing and building systems are just some of available strategies. Not only do they result in environmental savings, but also bring about financial benefits, related to lower water use fees, lower sewage volumes to treat and energy use reductions. (source: LEED Reference Guide, 2001:65) Installing more efficient fixtures, reducing or eliminating water usage for landscaping and playfields, and incorporating innovative wastewater technologies may all be opportunities to achieve points in this category. Energy & Atmosphere Buildings in the US account for more than 30% of the total energy use and for approximately 60% of electricity. 75% of energy is derived from the burning of fossil fuels, which releases CO2 into the Atmosphere and contributes to global warming. Moreover, coal fired electric utilities release nitrogen oxides and sulfur dioxide, where the former contribute to smog and the latter to acid rain. Other types of energy production are not less harmful. Burning of natural gas produces nitrogen oxides and greenhouse gases as well, nuclear power creates nuclear wastes, while hydroelectric generating plants disrupt natural water flows. Luckily there are several practices that can reduce energy consumption and are environmentally and economically beneficial. Not only will they reduce the air pollution and mitigate global warming thanks to being less dependent on power plants, but also they will reduce operational costs and will quickly pay back. In order to make the most of those practices, it’s important to adopt a holistic approach to the building’s energy load and integrate different energy saving strategies. (source: LEED Reference Guide, 2001:93) Replacement of the HVAC systems would be necessary to achieve many of the energy-related points in this category. Metering and commissioning should be included in those efforts. On-Site Renewable Energy credits may be attainable with wind or solar installations. The roof is equipped with solar panels that could qualify for renewable energy credits. Green Power credits may also be attainable. Material & Resources The steps related to process building materials, such as extraction, processing and transportation are not environmentally natural, as they pollute the air, water and use natural resources. Construction and demolition wastes account for 40% of the solid waste stream in the US. Reusing existing documents is one of the best strategies to reduce solid wastes volumes and prevents then from ending up at landfills. It also reduces habitat disturbance and minimizes the need for the surrounding infrastructure. While using new materials one should take into account different material sources. Salvaged materials provide savings on material costs, recycled content material minimizes waste products and local materials reduce the environmental impact of transportation. Finally, using rapidly renewable materials and certified wood decreases the consumption of natural resources. Recycling and reusing construction waste is another strategy to be taken into consideration in sustainable design. (source: LEED Reference Guide, 2001:167) Depending on future programmatic needs, it may be possible to renovate the building in such a way as to achieve Building Reuse credits. Construction Waste Management credits should be considered, but may be difficult to achieve due to the schools small town setting. Due to the age of the school, it is unlikely that many materials could be salvaged for reuse. However, replacement interior finishes can be specified in order to be compliant with LEED guidelines, including products that would help achieve Recycled Content, Regional Materials, and Rapidly Renewable Materials, and/or Certified Wood credits. Indoor Environmental Quality As we spend a big majority of our time indoors, the emphasis should be put on optimal indoor environmental quality strategies while (re)designing a building . Otherwise, a poor IEQ will have adverse effects on occupants’ health, productivity and quality of life. IEQ strategies such as ventilation effectiveness and control of contaminants or a building flush-out prior to occupancy can reduce potential liability, increase the market value of the building but can also result in a significantly higher productivity (16%). Other strategies involve automatic sensors and controls, introducing fresh air to the building or providing lots of daylighting views. (source: LEED Reference Guide, 2001:215) As noted in Energy & Atmosphere, replacement of the HVAC systems would be necessary to achieve several of these credits, including Outdoor Air Delivery Monitoring, Increased Ventilation, Controllability of Systems Thermal Comfort, both Thermal Comfort credits. The Low Emitting Materials credit could be achieved with proper specification of finishes and applications. Other credits in this category that could be realized are Controllability of Systems Lighting, both Daylight and Views, and Mold Prevention. Innovation & Design Process This category is aimed at recognizing projects that implemented innovative building features and sustainable building knowledge, and whose strategy or measure results exceeded those which are required by the LEED Rating System. Expertise in sustainable design is the key element of the innovative design and construction process. (source: LEED Reference Guide, 2001:271) For a major renovation project such as would be needed at the school, a LEED AP should be part of the A/E team and his or her inclusion would garner one ID point. The School as a Teaching Tool credit would be the next most easily achieved in this category. Instituting green cleaning strategies should also be considered.
Page 47
Report Generated at 23 Dec 2015 10:42
Justification for Allocation of Points
Building Name and Level:
Evening Street Elementary K-6
Building features that clearly exceed criteria: 1.
The facility is located within a residential neighborhood and is easily accessed.
2.
Physical education facilities provide adequate space and are well maintained.
3.
Exterior play areas are adequate and well maintained.
4. 5. 6. Building features that are non-existent or very inadequate: 1.
Overall building is not ADA accessible.
2.
The building is reported to contain asbestos and other hazardous materials.
3.
No counselor offices are observed.
4. 5. 6. Back to Assessment Summary
Justification for Allocation of Points
Page 48
Report Generated at 23 Dec 2015 10:42
Environmental Hazards Assessment Cost Estimates Owner: Worthington City Facility: Evening Street Elementary Date of Initial Assessment: Sep 23, 2015 Date of Assessment Update: Dec 22, 2015 Cost Set: 2015
District IRN: 45138 Building IRN: 10868 Firm: Van Auken Akins Architects
Scope remains unchanged after cost updates. Building Addition 1963 Original Construction 1988 Gym Wing Total Total with Regional Cost Factor (100.00%) Regional Total with Soft Costs & Contingency
Total of Environmental Hazards Assessment Cost Estimates Renovation Demolition 42,740 $68,634.00 $68,634.00 7,187 $718.70 $718.70 49,927 $69,352.70 $69,352.70 — $69,352.70 $69,352.70 — $86,295.77 $86,295.77
Addition Area (sf)
Page 49
Report Generated at 23 Dec 2015 10:42
Environmental Hazards(Enhanced) - Worthington City (45138) - Evening Street Elementary (10868) - Original Construction Environmental Hazards(Enhanced) - Worthington City (45138) - Evening Street Elementary (10868) - Original Construction
Owner:
Worthington City
Facility:
Evening Street Elementary
Bldg. IRN: BuildingAdd:
Date On-Site:
10868 Original Construction
Consultant Name:
A. Asbestos Containing Material (ACM) ACM Found 1. Boiler/Furnace Insulation Removal 2. Breeching Insulation Removal 3. Tank Insulation Removal 4. Duct Insulation Removal 5. Pipe Insulation Removal 6. Pipe Fitting Insulation Removal 7. Pipe Insulation Removal (Crawlspace/Tunnel) 8. Pipe Fitting Insulation Removal (Crawlspace/Tunnel) 9. Pipe Insulation Removal (Hidden in Walls/Ceilings) 10. Dismantling of Boiler/Furnace/Incinerator 11. Flexible Duct Connection Removal 12. Acoustical Plaster Removal 13. Fireproofing Removal 14. Hard Plaster Removal 15. Gypsum Board Removal 16. Acoustical Panel/Tile Ceiling Removal 17. Laboratory Table/Counter Top Removal 18. Cement Board Removal 19. Electric Cord Insulation Removal 20. Light (Reflector) Fixture Removal 21. Sheet Flooring with Friable Backer Removal 22. Fire Door Removal 23. Door and Window Panel Removal 24. Decontamination of Crawlspace/Chase/Tunnel 25. Soil Removal 26. Non-ACM Ceiling/Wall Removal (for access) 27. Window Component (Compound, Tape, or Caulk) - Reno & Demo 28. Window Component (Compound, Tape, or Caulk) - Reno Only 29. Resilient Flooring Removal, Including Mastic 30. Carpet Mastic Removal 31. Carpet Removal (over RFC) 32. Acoustical Tile Mastic Removal 33. Sink Undercoating Removal 34. Roofing Removal 35. (Sum of Lines 1-34) 36. (Sum of Lines 1-34)
AFM=Asbestos Free Material Status Quantity Unit Cost Estimated Cost Not Present 0 $10.00 $0.00 Not Present 0 $10.00 $0.00 Not Present 0 $8.00 $0.00 Not Present 0 $8.00 $0.00 Not Present 0 $10.00 $0.00 Assumed Asbestos-Containing Material 368 $20.00 $7,360.00 Not Present 0 $12.00 $0.00 Not Present 0 $30.00 $0.00 Not Present 0 $15.00 $0.00 Not Present 0 $2,000.00 $0.00 Not Present 0 $100.00 $0.00 Not Present 0 $7.00 $0.00 Not Present 0 $25.00 $0.00 Not Present 0 $7.00 $0.00 Not Present 0 $6.00 $0.00 Not Present 0 $3.00 $0.00 Not Present 0 $100.00 $0.00 Not Present 0 $5.00 $0.00 Not Present 0 $1.00 $0.00 Not Present 0 $50.00 $0.00 Not Present 0 $4.00 $0.00 Not Present 0 $100.00 $0.00 Not Present 0 $100.00 $0.00 Not Present 0 $3.00 $0.00 Not Present 0 $150.00 $0.00 Not Present 0 $2.00 $0.00 Not Present 0 $300.00 $0.00 Not Present 0 $300.00 $0.00 Assumed Asbestos-Containing Material 19000 $3.00 $57,000.00 Not Present 0 $2.00 $0.00 Not Present 0 $1.00 $0.00 Not Present 0 $3.00 $0.00 Not Present 0 $100.00 $0.00 Not Present 0 $2.00 $0.00 Total Asb. Hazard Abatement Cost for Renovation Work $64,360.00 Total Asb. Hazard Abatement Cost for Demolition Work $64,360.00
B. Removal Of Underground Storage Tanks Tank No. 1. (Sum of Lines 1-0)
None Reported Location
Age
Product Stored Size Total Cost For Removal Of Underground Storage Tanks
C. Lead-Based Paint (LBP) - Renovation Only 1. Estimated Cost For Abatement Contractor to Perform Lead Mock-Ups 2. Special Engineering Fees for LBP Mock-Ups 3. (Sum of Lines 1-2) D. Fluorescent Lamps & Ballasts Recycling/Incineration Area Of Building Addition 1. 42740 42740
Est.Rem.Cost $0.00
Addition Constructed after 1980 $0.00 $0.00 Total Cost for Lead-Based Paint Mock-Ups $0.00
Square Feet w/Fluorescent Lamps & Ballasts
Unit Cost $0.10
E. Other Environmental Hazards/Remarks 1. (Sum of Lines 1-0) 2. (Sum of Lines 1-0)
None Reported Cost Estimate $0.00 $0.00
Description Total Cost for Other Environmental Hazards - Renovation Total Cost for Other Environmental Hazards - Demolition
F. Environmental Hazards Assessment Cost Estimate Summaries 1. A35, B1, C3, D1, and E1 2. A36, B1, D1, and E2
Not Applicable Total Cost $4,274.00
Total Cost for Env. Hazards Work - Renovation Total Cost for Env. Hazards Work - Demolition
$68,634.00 $68,634.00
* INSPECTION ASSUMPTIONS for Reported/Assumed Asbestos-Free Materials (Rep/Asm AFM): a.
Unless reported otherwise by the District, materials installed after 1980 are assumed to be asbestos-free.
b.
Unless reported otherwise by the District, small quantities (less than 1,000 square feet) of the following materials are assumed to be asbestos free: hard plaster, acoustical plaster and gypsum board systems; acoustical panels and tiles; fireproofing; 12"×12" floor tile and mastic.
c.
Unless reported otherwise by the District, all roofing materials are assumed to be asbestos-free.
THESE MATERIALS SHOULD BE PROPERLY SAMPLED AND ANALYZED FOR ASBESTOS PRIOR TO DISTURBING THEM.
Page 50
Report Generated at 23 Dec 2015 10:42
Environmental Hazards(Enhanced) - Worthington City (45138) - Evening Street Elementary (10868) - Gym Wing Environmental Hazards(Enhanced) - Worthington City (45138) - Evening Street Elementary (10868) - Gym Wing
Owner:
Worthington City
Facility:
Evening Street Elementary
Bldg. IRN:
10868
BuildingAdd:
Date On-Site:
Gym Wing
Consultant Name:
A. Asbestos Containing Material (ACM) ACM Found 1. Boiler/Furnace Insulation Removal 2. Breeching Insulation Removal 3. Tank Insulation Removal 4. Duct Insulation Removal 5. Pipe Insulation Removal 6. Pipe Fitting Insulation Removal 7. Pipe Insulation Removal (Crawlspace/Tunnel) 8. Pipe Fitting Insulation Removal (Crawlspace/Tunnel) 9. Pipe Insulation Removal (Hidden in Walls/Ceilings) 10. Dismantling of Boiler/Furnace/Incinerator 11. Flexible Duct Connection Removal 12. Acoustical Plaster Removal 13. Fireproofing Removal 14. Hard Plaster Removal 15. Gypsum Board Removal 16. Acoustical Panel/Tile Ceiling Removal 17. Laboratory Table/Counter Top Removal 18. Cement Board Removal 19. Electric Cord Insulation Removal 20. Light (Reflector) Fixture Removal 21. Sheet Flooring with Friable Backer Removal 22. Fire Door Removal 23. Door and Window Panel Removal 24. Decontamination of Crawlspace/Chase/Tunnel 25. Soil Removal 26. Non-ACM Ceiling/Wall Removal (for access) 27. Window Component (Compound, Tape, or Caulk) - Reno & Demo 28. Window Component (Compound, Tape, or Caulk) - Reno Only 29. Resilient Flooring Removal, Including Mastic 30. Carpet Mastic Removal 31. Carpet Removal (over RFC) 32. Acoustical Tile Mastic Removal 33. Sink Undercoating Removal 34. Roofing Removal 35. (Sum of Lines 1-34) 36. (Sum of Lines 1-34)
Status Quantity Unit Cost Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Not Present 0 Total Asb. Hazard Abatement Cost for Renovation Work Total Asb. Hazard Abatement Cost for Demolition Work
AFM=Asbestos Free Material Estimated Cost $10.00 $0.00 $10.00 $0.00 $8.00 $0.00 $8.00 $0.00 $10.00 $0.00 $20.00 $0.00 $12.00 $0.00 $30.00 $0.00 $15.00 $0.00 $2,000.00 $0.00 $100.00 $0.00 $7.00 $0.00 $25.00 $0.00 $7.00 $0.00 $6.00 $0.00 $3.00 $0.00 $100.00 $0.00 $5.00 $0.00 $1.00 $0.00 $50.00 $0.00 $4.00 $0.00 $100.00 $0.00 $100.00 $0.00 $3.00 $0.00 $150.00 $0.00 $2.00 $0.00 $300.00 $0.00 $300.00 $0.00 $3.00 $0.00 $2.00 $0.00 $1.00 $0.00 $3.00 $0.00 $100.00 $0.00 $2.00 $0.00 $0.00 $0.00
B. Removal Of Underground Storage Tanks Tank No. 1. (Sum of Lines 1-0)
None Reported Location
Age
Product Stored Size Total Cost For Removal Of Underground Storage Tanks
C. Lead-Based Paint (LBP) - Renovation Only 1. Estimated Cost For Abatement Contractor to Perform Lead Mock-Ups 2. Special Engineering Fees for LBP Mock-Ups 3. (Sum of Lines 1-2) D. Fluorescent Lamps & Ballasts Recycling/Incineration Area Of Building Addition 1. 7187 7187
$0.00
Addition Constructed after 1980 $0.00 $0.00 Total Cost for Lead-Based Paint Mock-Ups $0.00
Square Feet w/Fluorescent Lamps & Ballasts
E. Other Environmental Hazards/Remarks 1. (Sum of Lines 1-0) 2. (Sum of Lines 1-0)
Est.Rem.Cost
None Reported Cost Estimate $0.00 $0.00
Description Total Cost for Other Environmental Hazards - Renovation Total Cost for Other Environmental Hazards - Demolition
F. Environmental Hazards Assessment Cost Estimate Summaries 1. A35, B1, C3, D1, and E1 2. A36, B1, D1, and E2
Not Applicable Total Cost $718.70
Unit Cost $0.10
Total Cost for Env. Hazards Work - Renovation Total Cost for Env. Hazards Work - Demolition
$718.70 $718.70
* INSPECTION ASSUMPTIONS for Reported/Assumed Asbestos-Free Materials (Rep/Asm AFM): a.
Unless reported otherwise by the District, materials installed after 1980 are assumed to be asbestos-free.
b.
Unless reported otherwise by the District, small quantities (less than 1,000 square feet) of the following materials are assumed to be asbestos free: hard plaster, acoustical plaster and gypsum board systems; acoustical panels and tiles; fireproofing; 12"×12" floor tile and mastic.
c.
Unless reported otherwise by the District, all roofing materials are assumed to be asbestos-free.
THESE MATERIALS SHOULD BE PROPERLY SAMPLED AND ANALYZED FOR ASBESTOS PRIOR TO DISTURBING THEM.
Page 51
Report Generated at 23 Dec 2015 10:42